Facility CDU 8 MW
8.15 MW of heat transfer from a single unit with a 2 °C approach. Installed outside the white space, feeding the halls through a dual-loop design.

Designed for the AI hall.
Dual loop
Separates the facility and secondary loops, protecting the TCS and the IT hardware on it.
AT2 heat exchanger
A 2 °C approach for warm-water cooling and heat reuse.
Smart pumping
Four VFD-driven pumps in N+1, with high head for large halls.
Self-monitoring
Leak detection, condensation management, coolant level control and water quality, built in.
Technical data.
- Heat transfer
- 8,156 kW
- Approach
- 2 °C (AT2)
- Architecture
- Dual loop, facility to secondary
- Rack density
- Racks above 100 kW
- Pumps
- 4 × VFD-driven, N+1 (3+1)
- Pump power
- 3 × 31.8 kW running
- Head
- High-head design
- Supply
- 3 × 380–480 V AC, 50/60 Hz
- L × W × H
- 4,860 × 1,800 × 2,406 mm
- Weight
- 9,877 kg transport, 12,037 kg filled
- Location
- Outside the white space
- Interface
- 12-inch touchscreen HMI, remote monitoring
- Protection
- Leak detection, condensation management, coolant level control
- Protocols
- BACnet, Modbus, OPC UA, SNMP, PROFINET
- Monitored
- pH, conductivity, turbidity, glycol concentration, corrosion rate, temperature
- Treatment
- Chemical dosing and pH regulation built in
Figures are manufacturer nominal values. Final selection and performance are confirmed against your design conditions.
The unit, and everything around it.
Against your rack density, approach temperature and site.
Set in place, piped, insulated and clad by our crew.
The loop behind it cleaned, filled with PG25 and certified.
One record for unit, loop and fluid.
Sampling, top-up and support for the life of the loop.
Other units.

Facility CDU 5 MW

In-row CDU 1.4–2.6 MW

Dry cooler 2 MW
Specifying a hall?
Send us the load, the approach and the site. We come back with a selection within one business day.
- 01At design
The commissioning scope is right before the specification goes out.
- 02In construction
The flush and fill is programmed off the critical path.
- 03At handover
One certificate. The baseline you keep.